HIMA F8652E Redundant Safety CPU Module
- Product Code: F8652E
- Availability: In Stock
Purchase Attributes:Original, Brand New
Service Attributes
▷ Stock & Logistics:Fast Delivery
▷ After-sales Guarantee:12 Months Warranty
Manufacturer: HIMA Paul Hildebrandt GmbH, Germany
Part No: F8652E (Code:984865264)
Type: SIL3 Redundant Safety CPU Module for HIMax / H41q/H51q SIS System
Applicable: ESD / BMS / FGS Safety Instrumented System
HIMA F8652E
Manufacturer: HIMA Paul Hildebrandt GmbH, Germany
Part No: F8652E (Code:984865264)
Type: SIL3 Redundant Safety CPU Module for HIMax / H41q/H51q SIS System
Applicable: ESD / BMS / FGS Safety Instrumented System
1. Product Overview
F8652E is dual redundant safety central processor of HIMax safety platform, TÜV certified SIL3 per IEC61508/IEC61511, adopts dual-lockstep 32-bit processor architecture, responsible for safety logic operation, backplane bus communication and system fault diagnosis; supports hot redundant backup and online program download via SILworX, core controller for petrochemical, power plant SIS safety cabinet.
2. Core Technical Parameters
• Processor: Dual synchronous lockstep 32-bit CPU, 25MHz working frequency
• Memory:1MB Flash(OS)+512KB User Program Flash+256KB SRAM per core
• Power:24VDC(18~30VDC), typical operating current≈60mA
• Interfaces:2×RS485, onboard safety backplane bus, 4-digit LED diagnostic display
• Operating Temp:-20℃~+60℃, Storage:-40℃~+85℃, IP20 cabinet mounting
• Certification:SIL3,TÜV,CE; redundant fault-tolerant HFT1 safety design
3. Key Functional Features
• Lockstep dual-core real-time self-check, automatic fault switching between master/standby CPU
• Full system & channel diagnosis for I/O module short/open circuit failure
• Watchdog fail-safe output (max 500mA load) for safety interlock protection
• Hot-swappable, supports online configuration & program updating with SILworX software
4. Application Fields
• Refinery & petrochemical plant ESD emergency shutdown control system
• Thermal/gas power plant boiler BMS burner management interlock cabinet
• Onshore/offshore oil&gas FGS fire&gas safety monitoring system
HIMA © F8652E SIL3 Redundant Safety CPU Module for HIMax SIS